for on/off/floating:
- Power supply: 230VAC, 24VAC/DC, 120VAC - Tolerance: 10% - Output torque: 6N.m 10N.m - Run time: 30s ... 150s - Operating power: 6VA (singal-wire control 15VA) - Standstill power: 1 ... 3VA (singal-wire control 15VA) - Output angle: 90 (95 max) - Control signal: 2 point on/off control; 3&2 point on/off control - Universal coupling: 10 ... 16mm or 5 ... 11mm - Overload: automatic - Protection class: IP54 - Ambient conditions: -10 ... +55C 0 ... 90% RH - Noise level (max): 40db(A) - weight: 0.6 ... 1.2kg
for modulating:
- Power supply: 24VAC - Tolerance: 10% - Output torque: 6N.m 10N.m - Run time: 30s ... 150s - Operating power: 6VA - Standstill power: 1 ... 2VA - Output angle: 90 (95 max) - Control signal: DC0(2) ... 10V DC0(4) ... 20mA - Universal coupling: 6 ... 16mm or 5 ... 11mm - Overload: automatic - Protection class: IP54 - Ambient conditions: -10 ... +55C 0 ... 90% RH - Noise level (max): 40db(A) - weight: 0.8 ... 1.2kg
It's a key hydraulic balance product used for precise flow regulating of water pipelines system in HVAC application
controlling the cool/heat water through the fan coil unit